Reference › Magnet wire

Magnet Wire Tables

Enameled copper magnet wire, #10 to #40 AWG. Diameters, resistance and area are computed from the AWG definition and copper resistivity, then checked against a NEMA MW 1000 manufacturer table.

Copper magnet wire by AWG

Bare diameter: d = 0.005 in × 92(36−n)/39. Resistance at 20 °C from annealed copper at 100% IACS, ρ = 1.7241 × 10−8 Ω·m (10.371 Ω·cmil/ft). Heavy-build overall diameter is the NEMA MW 1000-2020 nominal from MWS Wire's Copper Magnet Wire Data. Turns per inch is computed as 1 ÷ heavy-build diameter, for one close-wound layer.

AWGBare (in)Bare (mm)Heavy OD (in)Ω/1000 ftΩ/kmArea (cmil)Turns/in (computed)A at 200 A/cm²*A at 400 A/cm²*
100.10192.5880.1050.99883.27710,3839.4910.521.0
110.090742.3050.09421.2604.1328,23410.68.3416.7
120.080812.0530.08421.5885.2116,53011.96.6213.2
130.071961.8280.07542.0036.5715,17813.35.2510.5
140.064081.6280.06752.5258.2854,10714.84.168.32
150.057071.4500.06033.18410.453,25716.63.306.60
160.050821.2910.05394.01513.172,58318.62.625.23
170.045261.1500.04825.06316.612,04820.72.084.15
180.040301.0240.04316.38520.951,62423.21.653.29
190.035890.91160.03868.05126.411,28825.91.312.61
200.031960.81180.034610.1533.311,02228.91.042.07
210.028460.72290.031012.8042.00810.132.30.8211.64
220.025350.64380.027616.1452.96642.436.20.6511.30
230.022570.57330.024920.3666.78509.540.20.5161.03
240.020100.51060.022325.6784.21404.044.80.4090.819
250.017900.45470.019932.37106.2320.450.30.3250.649
260.015940.40490.017840.81133.9254.156.20.2580.515
270.014200.36060.016151.47168.9201.562.10.2040.408
280.012640.32110.014464.90212.9159.869.40.1620.324
290.011260.28590.013081.83268.5126.776.90.1280.257
300.010030.25460.0117103.2338.5100.585.50.1020.204
310.0089280.22680.0104130.1426.979.7096.20.08080.162
320.0079500.20190.00940164.1538.363.211060.06410.128
330.0070800.17980.00840206.9678.850.131190.05080.102
340.0063050.16010.00750260.9856.039.751330.04030.0806
350.0056150.14260.00670329.01,07931.521490.03190.0639
360.0050000.12700.00600414.81,36125.001670.02530.0507
370.0044530.11310.00550523.11,71619.831820.02010.0402
380.0039650.10070.00490659.62,16415.722040.01590.0319
390.0035310.089690.00430831.82,72912.472330.01260.0253
400.0031450.079870.003801,0493,4419.8882630.01000.0200

*Current at a winding current density, not an ampacity rating. Transformer and inductor designers size windings by current density. McLyman gives the rule of thumb 500 circular mils per amp ≈ 400 A/cm² and 1000 circular mils per amp ≈ 200 A/cm² (Transformer and Inductor Design Handbook, 3rd ed., ch. 4, PDF). The columns are bare copper area × current density, and agree within 3% with the 200 and 400 A/cm² columns of the Magnetics Inc. Wire Table.

Rules of thumb that follow from the AWG formula: every 3 gauges halves the area and doubles the resistance, and every 6 gauges halves the diameter. #10 is about 1 Ω per 1000 ft (MWS: 0.9988 Ω).